Sustainability includes saving dollars and not just resources

Corporate Client

DeFeo Associates helped this corporate client identify specific energy conservation measures and provided them with information that allowed for informed decisions regarding energy and sustainability.

Current & Proposed Energy Usage CO2 Reduction and Cost Analysis - HVAC

(Sample of Actual Work)

MonthCurrentCurrentCurrentCostProposedProposedProposedAnnual Cost
ThermsKWKWHThermsKWKWHSavings
1281.756516.4 199,042 $20,554.64 281.756 466.3 130,100 $6,989.62
2319.463618.7 224,344 $22,991.01 319.463 558.7 146,639 $7,837.64
3362.753670.4 279,911 $28,412.10 362.753 605.4 182,959 $9,684.28
4299.272640.2 215,963 $23,012.65 299.272 578.1 141,160 $7,836.74
5268.667520.9 188,700 $20,121.97 268.667 470.4 123,341 $6,850.34
6305.551451.0 216,452 $22,674.56 305.551 407.3 141,480 $7,731.19
7276.004446.9 213,828 $28,582.38 276.004 403.6 139,765 $9,799.48
8250.009578.6 231,329 $31,546.02 250.009 522.5 151,204 $10,834.30
9242.070458.9 213,549 $29,775.15 242.070 414.4 139,583 $10,214.24
10264.460397.6209,172$24,307.67264.460359.0136,721$8,316.27
11287.825441.6190,079$19,503.85287.825398.8124,242$6,665.80
12283.076534.9196,823$19,747.45283.076483.0128,650$6,717.83
Total3,440.906670.42,579,194$291,229.453,440.906605.41,685,844$99,477.73
 
CO2
Analysis
(lbs)
Current
Emissions
Current
Emissions
Proposed
Emissions
Proposed
Emissions
Total Annual
CO2
Reductions
40,2592,966,07340,2591,938,7201,027,353

Notations
1: Electric Costs are presented as an average of all electric cost functions.
2: CO2 Emissions are based on: 1.15 lbs/KWH; 11.7 lbs/therm

ENERGY CONSERVATION MEASURES - LIGHTING ANNUAL SAVINGS AND CO2 IMPACTS

ECMCostEnergy ReductionCost SavingPaybackCO2 Reduction
KWHYears(lbs)
Manual Controls
Automated Controls$5,50037,978$4,1781.3243,674
Ballasts/T-8 Lighting (8')
Ballasts/T-8 Lighting (4')$600524$5810.41602.83
Ballasts/T8 Lighting (2')
CFL$16810,901$1,1990.1412,536
HID
Total49,403$5,43456,813

Notations
1: Automated controls estimated at $100/each - 110 controls installed
2: Manual Controls estimated for lights on 24 hours/day
3: T-8 Lighting estimated at $300 each for 8' / $150 ea for 4' and u tube
4: Energy savings for automatic controls estimated at 25%
5: Energy savings for T-8 lighting estimated at 20% for utube and 4'; 38% for 8' based on 59 watt bulb
6: Energy savings for CFL estimated at 70%.
7: All savings assumed as independent measures.

How A Building's Design Can Waste Energy

Room Not Using Electricity EfficientlyNone of the outside rooms in this building take advantage of natural light. Although the building is configured with a large number of rooms on outside walls, each of the rooms is sealed. This is indicative of the period in which the building was constructed, but consumes a large amount of electricity for no practical reason given current construction options.